NJREC 72.5 kV wall bushings carry a conductor through a grounded wall or partition while insulating it from the structure. This air-to-air design is specified with an equipment highest voltage (Um) of 72.5 kV under IEC 60137:2017 and a maximum rated current of 4000 A. For new projects or replacements, confirm the mounting and connection dimensions against the installation drawing.


| Parameter | Unit | IEC 60137:2017 72.5 kV |
|---|---|---|
| Highest voltage for equipment Um | kV | 72.5 |
| Rated frequency | Hz | 50/60 |
| Dry power frequency withstand voltage, 1 minute | kV | 140 |
| Lightning impulse withstand voltage (BIL) | kV | 325 |
| Switching impulse withstand voltage (SIL) | kV | – |
| Maximum rated current | A | 4000 |
| Temperature range | °C | Down to −60 °C and up to +55 °C available on request |



A 72.5 kV indoor-to-outdoor wall bushing can be specified where a conductor passes from an enclosed electrical room to an outdoor connection. Identify the exposed side and installation environment so the housing and insulation arrangement can be confirmed for the selected model.
For a connection between indoor areas, a wall feedthrough insulator separates the live conductor from the surrounding wall or grounded barrier. Check the wall opening, mounting dimensions and terminal positions, especially when replacing an existing unit.
NJREC offers a 72.5 kV IEC wall bushing option with a maximum rated current of 4000 A. The conductor, terminals, mounting flange, wall thickness and insulation arrangement can be checked against the project requirements and installation drawing.
For a replacement wall bushing, NJREC can review the original unit’s mounting flange, wall thickness, conductor connections and dimensions on both sides to check fit and electrical compatibility.
The 1-minute dry power frequency withstand voltage is 140 kV, and the lightning impulse withstand voltage (BIL) is 325 kV.
The maximum rated current shown for the 72.5 kV IEC option is 4000 A. Confirm the required current and connection details for the selected model.
Fit must be checked against the mounting and terminal dimensions. Send the existing drawing, wall thickness and opening size for review.
Yes. The 72.5 kV wall bushing can be configured for an indoor-to-outdoor connection. Please provide the wall dimensions and identify which side is exposed outdoors.