NJREC supplies high-current transformer bushings primarily with OIP or RIP condenser cores. RIS condenser-core designs are also available. The bushings use porcelain housings.These capacitive bushings carry high current through the transformer tank while insulating the conductor from the grounded structure.
NJREC offers IEC high-current bushings from 24 kV to 52 kV and IEEE high-current bushings from 25 kV to 46 kV, with rated current options of 10,000 A, 16,000 A, 25,000 A and 31,500 A. The OIP and RIP bushing options combine a condenser insulation core with a porcelain exterior for high-current transformer connections.


NJREC offers 24 kV, 36 kV and 52 kV high-current condenser bushings with OIP or RIP cores and porcelain housings. The IEC specification range references IEC 60137-2017 and includes rated currents from 10,000 A to 31,500 A.
| Standard | IEC 60137-2017 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Highest Voltage for Equipment Um | kV | 24 | 24 | 24 | 24 | 36 | 36 | 36 | 36 | 52 | 52 | 52 | 52 |
| Rated Frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 |
| 1-Minute Dry Power-Frequency Withstand Voltage | kV | 55 | 55 | 55 | 55 | 77 | 77 | 77 | 77 | 105 | 105 | 105 | 105 |
| Lightning Impulse Withstand Voltage (BIL) | kV | 125 | 125 | 125 | 125 | 170 | 170 | 170 | 170 | 250 | 250 | 250 | 250 |
| Rated Current | A | 10000 | 16000 | 25000 | 31500 | 10000 | 16000 | 25000 | 31500 | 10000 | 16000 | 25000 | 31500 |
| Temperature Range | °C | Down to −60°C up to +55°C available on request | |||||||||||
NJREC offers 25 kV, 34.5 kV and 46 kV high-current transformer bushings with OIP or RIP condenser insulation and porcelain housings. The IEEE specification range references IEEE C57.19.01-2017 and includes rated currents from 10,000 A to 31,500 A.
| Standard | IEEE C57.19.01-2017 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Highest Voltage for Equipment Um | kV | 25 | 25 | 25 | 25 | 34.5 | 34.5 | 34.5 | 34.5 | 46 | 46 | 46 | 46 |
| Rated Frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 |
| 1-Minute Dry Power-Frequency Withstand Voltage | kV | 60 | 60 | 60 | 60 | 80 | 80 | 80 | 80 | 105 | 105 | 105 | 105 |
| Lightning Impulse Withstand Voltage (BIL) | kV | 150 | 150 | 150 | 150 | 200 | 200 | 200 | 200 | 250 | 250 | 250 | 250 |
| Rated Current | A | 10000 | 16000 | 25000 | 31500 | 10000 | 16000 | 25000 | 31500 | 10000 | 16000 | 25000 | 31500 |
| Temperature Range | °C | Down to −60°C up to +55°C available on request | |||||||||||



NJREC offers IEC high-current bushings at 24 kV, 36 kV and 52 kV, and IEEE high-current bushings at 25 kV, 34.5 kV and 46 kV. Each voltage class includes rated current options of 10,000 A, 16,000 A, 25,000 A and 31,500 A.
NJREC primarily supplies high-current bushings with OIP (oil-impregnated paper) or RIP (resin-impregnated paper) condenser cores. RIS (resin-impregnated synthetic) condenser-core designs are also available.
For IEC 24 kV, 36 kV and 52 kV bushings, the 1-minute dry power-frequency withstand voltages are 55 kV, 77 kV and 105 kV, and the lightning impulse withstand voltages are 125 kV, 170 kV and 250 kV, respectively. For IEEE 25 kV, 34.5 kV and 46 kV bushings, the corresponding power-frequency withstand voltages are 60 kV, 80 kV and 105 kV, and the lightning impulse withstand voltages are 150 kV, 200 kV and 250 kV.